GENERAL SPECIFICATIONS
Timers : 512
Counters : 512
Function Blocks : 512
Operation temp. : -20ºC-55ºC
Storage temp :-40ºC-70ºC
Protection : IP20(Non-waterproof)
RTC accuracy : MAX ±2S/day
RTC Backup at 25 °C : 20 days
Program and settings Backup :10 years
Data Power-off retentivity : 10 years
Dimensions : 95*90*67 (Unit, mm)
Certificate : CE
Installation : 35mm-DIN rail or screw for installation
Modify parameters via keypad LCD: yes
Password protection : 4-digit number password protection or disable program upload function
Communication interface : 1 Program/RS232 port ( TTL interface)
Communication protocol : Modbus RTU/ASCII
It's optional for xLogic to be either slave or master in Modbus network.
Technical Index
Dimension
Wiring Diagram
Timers : 512
Counters : 512
Function Blocks : 512
Operation temp. : -20ºC-55ºC
Storage temp :-40ºC-70ºC
Protection : IP20(Non-waterproof)
RTC accuracy : MAX ±2S/day
RTC Backup at 25 °C : 20 days
Program and settings Backup :10 years
Data Power-off retentivity : 10 years
Dimensions : 95*90*67 (Unit, mm)
Certificate : CE
Installation : 35mm-DIN rail or screw for installation
Modify parameters via keypad LCD: yes
Password protection : 4-digit number password protection or disable program upload function
Communication interface : 1 Program/RS232 port ( TTL interface)
Communication protocol : Modbus RTU/ASCII
It's optional for xLogic to be either slave or master in Modbus network.
Technical Index
Power supply: | |
Nominal voltage | DC 12-24V |
Operating limits | DC 10.8-28.8V |
Immunity from micro power cuts | Typ.5 ms |
Max. Startup current | Max. 0.5A |
Max. absorbed power | Normal: 3.5 W (10.8V dc) ; 4 W (28.8V dc) Transient Current: Max. 1A (DC12V) |
Protection against polarity inversions | Yes |
Input parameters: | |
Input No | 4 (2pt100+ I3-I4 ) |
Digital input | 2 ( I3-I4 ) |
Analogue input | 2 PT100 |
Digital inputs( I3-I4 ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC; <1mA |
Input signal1 | > 8 V DC;>1.7mA |
Input current | 2.3mA @ 10.8V dc 2.6mA @ 12.0 V dc 5.2 mA @ 24 V dc 6.3 mA @ 28.8 V dc |
Response time | 0 to 1 :<1 ms ;1 to 0 :<1 ms |
Maximum counting frequency | None |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
analog inputs( AI1-AI2 ) | |
Input No | 2 (AI1 -AI2) |
Digital input | None |
Analogue input | 2 Channels PT100 |
Resolution | 0.3ºC |
Measuring range | -50ºC to +200ºC |
Cable length | 10 m max. shielded and twisted |
Output parameters: | |
Output No. | 4 (Q1-Q4) |
Output type | 4 Relay output |
Continuous current | Resistive load 10A/Inductive load 2A |
Max. breaking voltage | AC 250 V DC 30 V |
Max. Allowable Power Force | 1250VA 300W |
Electrical durability Expectancy | 105 Operations at Rated Resistive Load |
Mechanical life | 107 Operations at No Load condition |
Response time | Operate Time : 15 mSec. Max. Release Time : 10 mSec. Max. |
Built-in protections | Against overloads and short-circuits: No Against overvoltages (*): No |
Galvanic isolation | None |
Switch frequency: | |
Mechanism | 10Hz |
Resistor/light load | 2Hz |
Sensitive load | 0.5Hz |
Wireless technology | |
Type of mobile wireless service | SMS, GPRS |
Type of mobile network / is supported | GSM, UMTS, LTE |
Operating frequency
| B1/B3/B5/B7/B8/B20 B1/B5/B8 850/900/1800/1900Mhz |
Other parameters: | |
Ethernet interface | No |
Voice alarming | No |
Weight |
Dimension
Wiring Diagram